12-1600.16 FIRE PROTECTION
Unofficial copy. It may be out of date. Not legal or zoning advice. Zoning rules change, and only the city or county can say for sure what is allowed on a property. Confirm with the city or county planning department before you buy, sign or build.
The official Marysvale code is at https://marysvale.gov/wp-content/uploads/2024/12/dec-15-2024-Full-section-12-Ordinance.pdf.
Text pulled 2026-10-19 from this source.
Tables (like use tables) may not copy cleanly, so check any table against the official code.
Confirm anything here with Marysvale planning before you rely on it.
1.
Requirements. All subdivisions shall have a fire protection plan prepared
by a licensed engineer and approved by a State, County, or Town fire
official prior to consideration by the ALUA.
2.
Compliance. All fire flow, line size, and hydrant standards shall conform
to the International Fire Code.
3.
Line Size. Water distribution lines in all subdivisions shall be a minimum
of 8 inches in diameter. Minimum line sizes may be increased to provide
for required fire flow of at least 500 gallons per minute (GPM).
4.
Loops and Valves. Water systems shall be looped when possible and
valves shall generally be spaced such that a break in any one length of
main will put no more than 1,000 feet out of service during repairs.